Final | 8/3/2020 | 8/4/2020 | 8/4/2020 | A | CANC |
Eric Story
|
|
|
Final inspection for the Apollo Lot. Contact onsite electrician Rod Tomlinson. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek No final given until service is energized
|
Permanent Service | 8/4/2020 | 8/4/2020 | 8/4/2020 | P | PASS |
Eric Story
|
|
|
Final inspection for the Apollo Lot. Contact onsite electrician Rod Tomlinson. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Meter main replaced with a main rated at 20K p/s u/g n ok
|
Final | 7/23/2020 | 7/24/2020 | 7/24/2020 | A | FAIL |
Eric Story
|
|
|
Final inspection at Apollo Parking Lot Contact Rod Tomlinson Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek AFC calc posted is 20,818 and main breaker rated at 10,000 Must replace main with a 25,000 frame
|
Permanent Service | 7/15/2020 | 7/16/2020 | 7/16/2020 | A | FAIL |
Eric Story
|
|
|
Service inspection. Call Rod Tomlinson with questions. Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek AFC calc shall be posted proir to service energized
|
Electrical Rough-In | 5/28/2020 | 5/29/2020 | 5/29/2020 | A | CANC |
Eric Story
|
|
|
Underground inspection. Contact electrician Rod Tomlinson with questions. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
|