Final | 2/28/2020 | 2/28/2020 | 2/28/2020 | P | PASS |
Rock A. Hudson
|
|
|
Correction complete, Final ok
|
Final | 2/25/2020 | 2/28/2020 | 2/28/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### 250.28- Main bonding jumper shall be installed as per manufacturers instructions.
|
Final | 2/20/2020 | 2/21/2020 | 2/21/2020 | P | NR |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### Needed permanent service inspection.
|
Permanent Service | 2/21/2020 | 2/21/2020 | 2/21/2020 | P | PASS |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### Minimum work space shall be provided as per 110.26. Work bench present in front of panel location. Ground rods shall be flush or recessed in ground as per 250.53(G). About 10" above grade at time of inspection. At time of inspection grounding electrode installed and service entrance conductors being installed. All branch circuits still need to be installed in new main breaker panel. p/s u/g rec ok
|