Final | 3/19/2020 | 3/19/2020 | 3/19/2020 | P | PASS |
Tom Saunders
|
|
|
Contact Ryan Wiedrich Phone #: ###-#### Inspection requested via web by Scott Campbell...complete...ok to final...card signed
|
Final | 3/17/2020 | 3/17/2020 | 3/17/2020 | P | PART |
Tom Saunders
|
|
|
QEI contact is Ryan Wiedrich. ###-####. He will be onsite the p.m. Phone #: ###-#### Inspection requested via web by Scott Campbell.. not all corrections complete...HVAC mini split unit still needs addressed...proper power feed and OCPD
|
Final | 3/16/2020 | 3/16/2020 | 3/16/2020 | P | FAIL |
Tom Saunders
|
|
|
bILL Phone #: ###-####... TCO ok for new areas and breakroom FAIL... 1) hard wired appliance shall have disconnect within sight...new water heater 2) new minisplit circuit not rated for nameplate rating...MOCP and MCA not met 3) all disconnects shall be labelled with panel location and branch circuit ..mini split 4) panel circuits shall be labelled with their clear and specific purpose
|
Electrical Rough-In | 3/4/2020 | 3/5/2020 | 3/5/2020 | A | PASS |
Tom Saunders
|
|
|
Site Contact is Ryan Weidrich Phone #: ###-#### Inspection requested via web by Scott Campbell...ok to cover new walls of office-switch and one outlet
|
Electrical Rough-In | 2/24/2020 | 2/24/2020 | 2/24/2020 | P | PASS |
Rock A. Hudson
|
|
|
CONTACT IS RYAN WEIDERICH Phone #: ###-#### Inspection requested via web by Scott Campbell City approved set of prints on site. Copy room walls only rough in ok cover.
|