Final | 5/7/2020 | 5/7/2020 | 5/7/2020 | P | PASS |
Tom Saunders
|
|
|
Contact: Matt Cinko. Please call 30 minutes before going Phone #: ###-#### Inspection requested via web by Deb Gooden...corrections made...ok to final
|
Final | 2/27/2020 | 2/28/2020 | 2/28/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Brian Gee.... call before going so Brian can meet you there please Phone #: ###-#### Inspection requested via web by Deb Gooden Relocated 2'x4' layin luminaire to for new walls. Park on south side for nearest entrance. 314.23- Boxes shall be secured to structure. Contractor supplied ladder, found boxes hanging on MC cable and EMT conduit. 400.12- Flexible cords shall not be installed above ceiling grid. Game area has receptacle located in ceiling with 2 extension cords plugged and routed above grid to unknown locations.
|