Permit Information
Permit NumberELE20-00943
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 1415 E BANNOCK ST
Project Name 
Customer NumberdeBelloy
ePlanReviewNo
Description
Alteration or Repair: New overhead service & knob & tube delete
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/5/20206/8/20206/8/2020APASS
DetailsJames Ady
Please call Kevin ###-#### on your way to meet you there. If you have any questions please feel free to contact Jason ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Corrections made final ok
Final6/4/20206/5/20206/5/2020AFAIL
DetailsJames Ady
Please call Kevin ###-#### with a heads up to meet you there. If you have any questions please feel free to contact Jason ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 356.12(1) LFMC shall not be ran where exposed to physical damage. (Seal tight accross walk way to tub) 680.26B7. All metal parts within 5ft of tub shall be bonded to tub. (Remove or bond 1in emt to tub) 334.1 NM cable shall terminate in box(14-2 hanging in basement near door way. 110.3 Dead recep in crawl next to door way
Electrical Rough-In4/3/20204/6/20204/6/2020APASS
DetailsMark Moncarr
This is for underground. Call Jason ###-#### for an inspection he will have access. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Trench was covered. Contractor sent a video. Depth as per NEC.
Electrical Rough-In3/24/20203/25/20203/25/2020APASS
DetailsJames Ady
Lock box code 6360. If you have any questions please feel free to contact Jason ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Complete rewire. Most areas fished in. Rough in ok
Permanent Service3/17/20203/19/20203/19/2020PPASS
DetailsJames Ady
Please call Jason with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan Meter/Main mounted, Grounding done, Mast in place, Guy wire kit onsite, Service entrance being installed at time of inspection. p/s o/h rec ok
Permanent Service3/17/20203/19/20203/17/2020PCANC
DetailsJames Ady
Someone will be there, please call Fred with any questions at ###-#### Phone #: ###-#### >> Inspection requested via web by Clayton Morgan Inspection cancelled from web by: Clayton Morgan