Permit Information
Permit NumberELE20-00944
StatusFinaled
Name KAHALA ELECTRIC LLC
Site Address 199 E MELROSE ST
Project Name 
Customer Number00024
ePlanReviewNo
Description
Alteration or Repair: Separate meter into 2
Seperate 2 kitchen circuits to 4
Add bath GFCI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/30/20203/31/20203/31/2020APASS
DetailsJames Ady
N/A Phone #: ###-#### Inspection requested via web by Aaron Decker Service only Final ok
Electrical Rough-In3/26/20203/27/20203/27/2020PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Aaron Decker
Panel wall ok to cover
Permanent Service3/27/20203/27/20203/27/2020PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Aaron Decker
Service already energized proir to inspection
p/s oh rec ok 2 meters
Rough-In Permanent Service3/24/20203/25/20203/25/2020APASS
DetailsJames Ady
Either AM or PM Inspection requested via web by Aaron Decker Contractor disconnected ID power feed and reconnected prior to inspection. 250.24A1 Groundng electrode conductor shall be connected to the same terminal or bus to which the grounded service conductor is connected at the service disconecting means. (Move grounding electrode conductor from sub panel to main disc. on exterior of building)
Rough-In Permanent Service3/23/20203/23/20203/23/2020PCANC
DetailsEric Story
Rough-in of panel wall for Idaho Power turn on. Call 30 minutes pre-inspection
for access instructions Phone #: ###-#### Inspection requested via web by Aaron Decker
Need grounds and neutrals seperated on sub panels
Remove bonding jumper and re-routte grounding electrode system to main panel where bonding is located
Conference3/16/20203/18/20203/18/2020APASS
DetailsJames Ady
Thank You! Phone #: ###-#### Inspection requested via web by Aaron Decker Discussed seperation of 2 Dweling inits. 2 meter pack with 2 100A sub panels.