Final | 6/8/2020 | 6/8/2020 | 6/8/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg...corrections made...ok to final
|
Final | 6/5/2020 | 6/5/2020 | 6/5/2020 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg... 1) all mechanical elements used to terminate a grounding electrode conductor or bonding jumper to a grounding electrode shall be accessible...250.68 2) riser shall be strapped within 3ft of meter
|
Permanent Service | 4/27/2020 | 4/27/2020 | 4/27/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg.... correction made uffer connection shall be accessible at final p/s u/g new ok...back of property
|
Electrical Rough-In | 4/22/2020 | 4/23/2020 | 4/23/2020 | A | PART |
Rock A. Hudson
|
|
|
Detached shop 200 amp service Phone #: ###-#### Inspection requested via web by jamie berg Panel location moved due to stairs, SER installed on interior of shop to new location. 230.6, 230.70(A)(1)- Service disconnecting means shall be located on the outside of a structure or immediately upon entering structure. Except electrical service wall, rest of shop rough in ok cover
|