Final | 6/5/2020 | 6/5/2020 | 6/5/2020 | P | PASS |
Rock A. Hudson
|
|
|
Bruce is on site contact Phone #: ###-#### Inspection requested via web by JENNY EMEL No card posted. Final ok
|
Final | 4/3/2020 | 4/3/2020 | 4/3/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Final inspection for elevator / chair lift electrical only - elevator / chair lift installed by others Bruce is on site - call hi, when you arrive and he will give you instructions on location of chair lift Phone #: ###-#### Inspection requested via web by JENNY EMEL 620.5- Work clearances for lift disconnecting means shall comply with 110.26. Fused disconnect located 6' back inside beautiful metal door and frame work. A rail is located in the middle of disconnecting means. 620.51(C)- Lift disconnecting means shall be located where readily accessible. Around corner towards meter base ok due to very limited space.
|