Permanent Service | 8/10/2020 | 8/10/2020 | 8/10/2020 | P | PASS |
Mark Moncarr
|
|
|
Service Inspection - Call Cory Sells if questions. Phone #: ###-#### Inspection requested via web by Shane Dale Service sticker located on inside panel. p/s u/g n ok
|
Electrical Rough-In | 7/16/2020 | 7/17/2020 | 7/17/2020 | A | PASS |
Mark Moncarr
|
|
|
Wall rough in inspection. Phone #: ###-#### Inspection requested via web by Shane Dale Ok cover remaining walls and ceilings for E side of building
|
Electrical Rough-In | 7/8/2020 | 7/9/2020 | 7/9/2020 | A | PASS |
Tom Saunders
|
|
|
Pole base inspection. Call Cory Sells if questions - ###-#### Phone #: ###-#### Inspection requested via web by Shane Dale...qty 4-ok to pour
|
Electrical Rough-In | 5/12/2020 | 5/12/2020 | 5/12/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale...underslab ground work...ok to cover
|
Rough-In Permanent Service | 4/10/2020 | 4/13/2020 | 4/13/2020 | A | PASS |
Rock A. Hudson
|
|
|
Ufer inspection for Monday morning. Question call Kory at ###-#### Phone #: ###-#### Inspection requested via web by Davin Moore Concrete encased electrode located on east end, rough in ok cover
|