Final | 4/21/2020 | 4/23/2020 | 4/23/2020 | A | PASS |
Tom Saunders
|
|
|
9am to 10am is preferable customer works early PM. we filled out panel schedule Phone #: ###-#### Inspection requested via web by Danielle Henderson...corrections made...per covid19 inspection requirements images were sent...ok to final
|
Final | 4/15/2020 | 4/16/2020 | 4/16/2020 | A | FAIL |
Tom Saunders
|
|
|
Mrs. Talbot works in the early PM, 9-10 am is preferable time slot if possible. Phone #: ###-#### Inspection requested via web by Danielle Henderson...
1) new panel..every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use...408.4
|
Final | 4/10/2020 | 4/15/2020 | 4/15/2020 | P | CANC |
Tom Saunders
|
|
|
If first number doesn''t work call ###-####. Also please call an hour before, and/or when he knows hes headed over. Phone #: ###-#### Inspection requested via web by Danielle Henderson...not ready...scheduled once power restored
|
Permanent Service | 4/13/2020 | 4/15/2020 | 4/15/2020 | P | PASS |
Tom Saunders
|
|
|
Main Panel Upgrade - Existing Main Panel is a Split-Bus Panel. Changing it out to a normal main breaker panel for solar connection later on, on a different permit ELE20-01287. Can you call ahead of time. Thanks. Phone #: ###-#### Inspection requested via web by Danielle Henderson... panel changed out for bussing for solar install. Not sized larger p/s u/g reconnect ok
|