Electrical Rough-In | 8/6/2020 | 8/6/2020 | 8/6/2020 | P | PASS |
Tom Saunders
|
|
|
ok with video/photo // Leslie Phone #: ###-####...corrections made....ok to cover
|
Electrical Rough-In | 8/3/2020 | 8/5/2020 | 8/5/2020 | P | FAIL |
Tom Saunders
|
|
|
Screened- Leslie- Please call access Phone #: ###-####...
1) wiring methods for romex shall be to code stapling, cable laid flat, use of stack its where more than 3 wires, distance from edge of stud wiring thru attic above rafters/trusses
|
Permanent Service | 8/5/2020 | 8/5/2020 | 8/5/2020 | P | PASS |
Tom Saunders
|
|
|
Screened- Leslie- Please call access Phone #: ###-####... p/s o/h new ok
|
Conference | 7/29/2020 | 7/30/2020 | 7/30/2020 | A | PASS |
Tom Saunders
|
|
|
Homeowners Conference Leslie */Screened*/ Phone #: ###-####... answered questions on complete wiring of house...service requirements...pamphlet given
|
Conference | 7/9/2020 | 7/10/2020 | 7/10/2020 | P | DONE |
Daryl DeGrange
|
|
|
I need a pre-construction meeting because I am the owner builder doing the electrical. Phone #: ###-#### Inspection requested via web by Leslie Thompson Discussed with home owner electrical requirements wiring a single family dwelling. Required branch circuits, AFCI, GFCI, 1 1/4, drilling, nail plates when needed, receptacle spacing,TR, WR recepts, smoke/ carbon detector requirement,
|