Conference | 4/25/2020 | 4/27/2020 | 4/27/2020 | A | DONE |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Keith Chetta Discussed wiring size as per 550 and meeting min 100 amp feeder conductor sizing and may change terminations to 75 degree column for conduit sizing
|
Permanent Service | 4/23/2020 | 4/24/2020 | 4/24/2020 | A | FAIL |
Rock A. Hudson
|
|
|
The site is directly behind 2509 w Boise Ave. It is outside, clean and accessible by vehicle. Wanting meter pack energized. All meter sockets will be utilized except for the lower right hand location. Idaho Power will be adding an additional power pole where the 3” conduit stops Phone #: ###-#### Inspection requested via web by Keith Chetta 550.33(B)- Feeder conductors shall have a capacity of not less than 100 amp. Pedistal terminations rated at 60 degrees C, #3 copper minimum shall be used as per 310.15(B)(7). Underground performed under ELE19-01179. Issued MIS20-00132 for improvement must be approved by planning and zoning.
|
Permanent Service | 4/22/2020 | 4/23/2020 | 4/22/2020 | P | CANC |
Eric Story
|
|
|
The job site is directly behind 2509 w. Boise ave. Wanting all meter bases energized except for the bottom right hand corner. Site is accessible for vehicles, open air and clean. Phone #: ###-#### >> Inspection requested via web by Keith Chetta Inspection cancelled from web by: Keith Chetta
|