Electrical Rough-In | 6/27/2020 | 6/29/2020 | 6/29/2020 | A | PASS |
Eric Story
|
|
|
3366 is code for the contractor box right of the main door. Phone #: ###-#### Inspection requested via web by Jack Cowan
Corrections fixed-Rough-in ok to cover
|
Electrical Rough-In | 6/20/2020 | 6/22/2020 | 6/22/2020 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jack Cowan 300.4D Cables shall not be secured within 1 1/4in from face of stud. (Areas through out) 300.4A1 Cables ran through bored hole within 1 1/4in from face of the stud shall have nail plates. (Areas through out) 334.30 Flat cbles shall not be stapled on edge. (Areas through out) 210.52E3 Recep needed on back patio. 210.52 A2 2 receps needed along Living room window wall where concrete has been removed. 300.5B Interior of a conduit ran underground shall be considered a wet location 334.12B4 NM cable shall not be installed in a wet location. Smoke detectors shall be installed.
|
Rough-In Permanent Service | 5/26/2020 | 5/26/2020 | 5/26/2020 | P | PASS |
Eric Story
|
|
|
Side gate is open on the east. Service is in the back. This is a 200A Meter Main outside with one outlet. Then a 200A subpanel in the basement. Sliding glass door in the back of the house should be open. Only want to energize the service for power. Will request a rough-in later. Phone #: ###-#### Inspection requested via web by Jack Cowan p/s o/h n ok
|