Final | 7/22/2020 | 7/23/2020 | 7/23/2020 | A | PASS |
Rock A. Hudson
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
|
Rough-In Permanent Service | 5/7/2020 | 5/8/2020 | 5/7/2020 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard correction complete, R/I P/S u/g n ok
|
Rough-In Permanent Service | 5/4/2020 | 5/5/2020 | 5/5/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 110.3- Meter base can not listed to receive a 3" underground conduit. Unable to install meter cover due to conduit coupling. 300.4- Nail plates needed in laundry rm, rt of furnace kit side, left kit counter, nook under window, m. bed corner, spare bed, hall closet. 314.25- recessed con cover shall completely enclose box in family room.
|