Final | 7/23/2020 | 7/23/2020 | 7/23/2020 | P | PASS |
Tom Saunders
|
|
|
Please call Chris for final inspection of vanilla tenant space. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo...
core and shell complete...new service powered and new divided side repowered...no new wiring..ok to final
|
Permanent Service | 7/9/2020 | 7/9/2020 | 7/9/2020 | A | PASS |
Tom Saunders
|
|
|
Please call Chris for inspection of new services for vacant space lease area. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo...
p/s u/g new ok...2 meters...house CT and vanilla tenant CT
|
Permanent Service | 7/7/2020 | 7/7/2020 | 7/7/2020 | P | CANC |
Tom Saunders
|
|
|
Please call Chris to inspect service for energizing vacant vanilla space. Thanks! Phone #: ###-#### >> Inspection requested via web by Rafael Castillo Inspection cancelled from web by: Rafael Castillo
|
Electrical Rough-In | 6/2/2020 | 6/2/2020 | 6/3/2020 | A | PASS |
Tom Saunders
|
|
|
Please call Chris for inspection of grounding in concrete pad at main gear on exterior of the south side of building. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo...service grounding ok to cover
|
Conference | 5/27/2020 | 5/28/2020 | 5/28/2020 | A | PASS |
Tom Saunders
|
|
|
Pleas call Rafael to discuss bonding of new service, grounding requirements at exterior of building, and expansion fitting requirements. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo.... discussed above requirements...ID PWR make expansion joint requirement on underground feeds...grounding off both services using same grounding electrode system...bonding of building steel and main sprinkler riser pipe
|
Conference | 5/19/2020 | 5/20/2020 | 5/20/2020 | A | PASS |
Tom Saunders
|
|
|
Please call Chris to discuss above grid ceiling expectations for completion of this project. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo... discussed scope of work and work area discussed no code violation shall be retained opened areas of ceiling will be addressed but areas where ceiling not to be opened need not addressed or areas not working in
|