Permanent Service | 6/3/2020 | 6/3/2020 | 6/3/2020 | P | PASS |
James Ady
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 6/2/2020 | 6/3/2020 | 6/3/2020 | P | PASS |
James Ady
|
|
|
Douglas Phone #: ###-#### corrections made rough in ok
|
Electrical Rough-In | 5/22/2020 | 5/26/2020 | 5/26/2020 | A | FAIL |
James Ady
|
|
|
Doug Phone #: ###-#### 210.11C1. 2 small appliance circuits needed.(Circuits shall serve no others. Remove lighting from dining room.)210.19A1. Brach circuit ampacity of continuous and noncontinuous loads.(Dish/ disp shall be dedicated citcuit and not fed from lighting circuit) 210.52E3. Balcony shall have recep. 110.3 B. Equipment shall be installed as per manufacturers specs.(100 amp breaker installed in Meter main on a 50amp max location. Move breaker.)
|