Electrical Rough-In | 6/22/2020 | 6/22/2020 | 6/22/2020 | P | PASS |
Mark Moncarr
|
|
|
Bart Phone #: ###-#### Ok cover. Corrections made.
|
Electrical Rough-In | 6/17/2020 | 6/19/2020 | 6/19/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Screened- Bart Phone #: ###-#### 210.52(A)- Upstairs walls 2' or wider shall have receptacle outlets installed. 210.52(G)- All patios and decks shall have a receptacle outlet installed within its perimeter. 210.70- Each man door with grade level exterior access shall have an exterior light installed. 250.24- Grounding electrode shall bond grounded conductor in the main service disconnect and an equipment ground installed from service to sub-panel. 250.64- Connection to grounding electrode shall remain accessible. 300.4- Walk house for additional nail plates. 314.25- Complete cans and install all covers. * Empty smoke box in down front rm.
|
Electrical Rough-In | 6/12/2020 | 6/16/2020 | 6/16/2020 | P | NR |
Rock A. Hudson
|
|
|
Bart Phone #: ###-#### Turned into conference. Discussed secure MN cable in center of 2x4 studs, nail plates, intersystem bond, changing to PVC nipple to simplify grounding, garage door receptacle, door bell wiring, pantry counter top receptacle requirements, well lockout, basement may be sheet rocked but to remain unfinished, smoke and carbon monoxide detector wiring, readily accessible GFCI devices for christmas ect., grounding electrode conductor installation, sub panel feeders.
|
Conference | 6/9/2020 | 6/12/2020 | 6/12/2020 | A | PASS |
Rock A. Hudson
|
|
|
Bart Phone #: ###-#### Discussed code requirements for wiring entire house. Pamphlet given. Owner has good understanding for scope of work.
|