Permit Information
Permit NumberELE20-02300
StatusIssued
Name MOUNTAIN POWER ELECT
Site Address 200 W MYRTLE ST
Project Name 
Customer Number19-044
ePlanReviewNo
Description
New: Prove the electrical work associated with the garage TI scope of the 3rd and Myrtle project.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Conference8/13/20208/13/20208/13/2020PPASS
DetailsRock A. Hudson
Discuss grounding and bonding Phone #: ###-#### Inspection requested via web by Jason Parke Discussed the installation of a common grounding electrode conductor from level 1 service location to the other service locations and tapping off to provide a grounding electrode conductor to each service. As long as connection comply with 250.64 and are listed for grounding and bonding... plan looks good. Thanks.
Electrical Rough-In8/10/20208/10/20208/10/2020APASS
DetailsRock A. Hudson
Wall rough in at 3rd and 4th floor apartments Phone #: ###-#### Inspection requested via web by Jason Parke Levels 3 and 4 apartment walls rough in ok cover
Conference8/6/20208/6/20208/6/2020APASS
DetailsRock A. Hudson
Conference visit to discuss routing of feeders for 3rd and 4th floor apartments and the units 5/6/7/8 that sit above them and materials to be used. Also pre-inspect on 3rd and 4th floor apartment walls Phone #: ###-#### Inspection requested via web by Jason Parke Decided not to pre-inspect units, Discussed the wiring methods required when running from type 1 construction to type 3 construction. As per 338.10(B)(4) SE cable shall be installed as per 334 part 2.
334.10(5)- NM and SER cable OK to be installed in type 1 and 2 construction as long as installed in a raceway rated for these types of construction. As per annex E types 1 and 2 construction wiring methods shall be of non- combustible type. Flexible metal conduit OK. Short runs of conduits or raceways OK as per 300.10 ex1, 300.12, 300.16(B), bushing required where cable emerges for raceway. 250.86 ex2- addition bonding not required.
Electrical Rough-In7/20/20207/21/20207/21/2020PPASS
DetailsRock A. Hudson
Wall rough in at garage parking office/data rooms Phone #: ###-#### Inspection requested via web by Jason Parke Parking garage east rooms wall rough in ok cover.