Final | 8/11/2020 | 8/11/2020 | 8/11/2020 | P | CANC |
Mark Moncarr
|
|
|
Completed corrections. Phone #: ###-#### Inspection requested via web by Kendra Lanham
|
Final | 7/15/2020 | 7/16/2020 | 7/16/2020 | A | FAIL |
Mark Moncarr
|
|
|
2 separate garages off of exiting services for residences. Phone #: ###-#### Inspection requested via web by Kendra Lanham Power to existing detached garage with 2 seperate vehicle bays for renters is running overhead at a height of about 8ft. Needs to follow 225.17-.19 for overhead feeder masts. Contractor said would probably go underground instead. Also needs a single pole disconnect for each seperate space before equiptment.
|