Final | 7/21/2020 | 7/21/2020 | 7/21/2020 | P | PASS |
James Ady
|
|
|
Contact: Damonn Barr Phone #: ###-#### Inspection requested via web by Deb Gooden final ok
|
Permanent Service | 7/20/2020 | 7/20/2020 | 7/20/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Deb Gooden Contractor had grounding complete and Nuetral installed in Service mast at time of inspection. Was installing remaining conductors in mast when I left. p/s o/h rec ok
|
Conference | 7/20/2020 | 7/20/2020 | 7/20/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Discussed requiments of 250.140 existing 3 wire to range does not need updated if the grounded conductor is insulated and orginates in a main service panel. (#8 Bare solid will need replaced with #8 insulated)
|