Electrical Rough-In | 8/11/2020 | 8/12/2020 | 8/12/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 8/11/2020 | 8/11/2020 | 8/11/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 250.92- Non current carrying metal parts of furnace shall be connected to an equipment grounding conductor. 300.4- Wher NM cable s run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected form damage by nail plates. Several thru out. 300.15- Smoke wire level 1 shall terminate in a box. 314.17- Where NM enters furnace it shall be protected from abrasion by a bushing. 314.17(C)- Up master bath vanity can NM sheathing shall enter box a minimum of 1/4".
|