INSP - Final | 9/20/1996 | 9/23/1996 | 9/20/1996 | A | PASS |
Marv Burrus
|
|
|
REINSPECTION CORRECTIONS COMPLETED...MB
|
INSP - Final | 9/19/1996 | 9/20/1996 | 9/20/1996 | A | FAIL |
Marv Burrus
|
|
|
09/20/96 403 - NEC: 110-17(A): EXPOSED LIVE PARTS. NEC: 110-16: PROVIDE WORK SPACE ABOUT EQUIPTMENT. NEC: 110-16(A): HORIZONTAL WORK SPACE SHALL NOT BE LESSTHAN 30I
|
INSP - Electrical Rough-In | 3/11/1996 | 3/12/1996 | 3/12/1996 | A | PASS |
Marv Burrus
|
|
|
REINSPECTION completed corrections.
|
INSP - Ele Rough-In/Perm Svc | 3/6/1996 | 3/7/1996 | 3/7/1996 | A | PASS |
Marv Burrus
|
|
|
17 ROOMS 200 AMPS A/C Survey: 210-(B)(1): Shall not supply motor load circuit. (disposal). 300-4(A)(2): Steel plate shall protect cable from nails etc..
|