INSP - Final | 9/25/1996 | 9/25/1996 | 9/25/1996 | P | CANC |
|
|
|
given to Pat Lass
|
INSP - Ele Rough-In/Perm Svc | 8/22/1996 | 8/22/1996 | 8/22/1996 | P | PASS |
|
|
|
reinspection
|
INSP - Ele Rough-In/Perm Svc | 8/20/1996 | 8/21/1996 | 8/21/1996 | A | FAIL |
|
|
|
BUILDING PERMIT IS ON THE POWER POLE--ELECTRICAL PERMIT IS IN THE BOX IN THE HOUSE r/i - failed 250-119 require green grd. screw/ 320-20 boxes to be flush w/siding/ 370-18 pan bx liv rm require KO / 336-12 support cables under floor / 370-23-B secure box m/bath - wire out of box down bath P/S Grounding electrod- require #4 copper not 1/2 rebar - clean area where wire to be poured.
|
INSP - Ele Rough-In/Perm Svc | 8/15/1996 | 8/15/1996 | 8/15/1996 | P | FAIL |
Joe Ray
|
|
|
no address
|