Permit Information
Permit NumberELE96-03342
StatusFinaled
Name LYNN PROCTOR
Site Address 1430 E SHENANDOAH DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final1/9/19971/9/19971/9/1997PPASS
DetailsMarv Burrus
01/09/97 403 - HOT TUB , OUTSIDE POLE LIGHTING TO BE DONE BY OTHERS; NEW OTHER CORRECTIONS COMPLETED...MB
INSP - Final1/3/19971/6/19971/6/1997AFAIL
DetailsMarv Burrus
01/05/97 403 - rein NEC: 210-52 RECEPTICLE REQUIRED ON 2 FT. OF WALL SPACE. NEC: 680-12. PANELBOARD SHALL BE LOCATED WITHIN 5 FT. OF HOT TUB.
INSP - Final1/3/19971/3/19971/5/1997PCANC
DetailsMarv Burrus
01/03/97 403 - AROUND BACK ON RED WOOD DECK LOOK IN PLANTER HOLE IN BOTT JUST FINISHED SEALING FLOORS,RESCHEDULED FOR 1-06-97...MB
ELE - Partial final12/31/199612/31/19961/1/1997PNH
DetailsMarv Burrus
12/31/96 403 - FIRE DAMAGE/ PERMIT PULLED FOR 11 ROOMS ONLY. INTERIOR DO KEY NOT IN LOCATION WHERE INDICATED, LEFT CARD...MB
INSP - Electrical Rough-In10/9/199610/10/199610/10/1996APASS
DetailsJoe Ray
10/09/96 404 - FIRE DAMAGE