INSP - Permanent service | 10/31/1996 | 10/31/1996 | 10/31/1996 | P | PASS |
Marv Burrus
|
|
|
REINSPECTIION CORRECTIONS COMPLETED...MB
|
INSP - Permanent service | 10/29/1996 | 10/29/1996 | 10/29/1996 | P | FAIL |
Marv Burrus
|
|
|
NEC: 230-6(2). service raceway encased in 2inches thick concrete. BCC..SHALL USE RIDGID METAL CONDUIT OR I.M.C. CONDUIT,(OPTION). UNDERGROUND RACEWAY INSIDE GARAGE WALL. SERVICE ENTERANCE CONDUCTOR
|
INSP - Permanent service | 10/22/1996 | 10/23/1996 | 10/23/1996 | A | FAIL |
Marv Burrus
|
|
|
10/23/96 403 - LATE AM PLEASE/ THIS IS THE ONE JERRY FROM BULLET TALKED NOT DONE YET, PERM SERVICE ON ONE WALL THAT IS THERE STOP-WORK...NO JOURNEYMAN ON JOB. MB.
|