INSP - Final | 4/9/1997 | 4/9/1997 | 4/9/1997 | P | PASS |
Marv Burrus
|
|
|
04/09/97 403 - REINSPECTION CORRECTIONS COMLETED...MB
|
INSP - Final | 4/8/1997 | 4/8/1997 | 4/8/1997 | P | FAIL |
Marv Burrus
|
|
|
04/08/97 403 - NEC: 370-18. UNUSED OPENINGS IN BOXES SHALL BE CLOSED. BOXES SHALL HAVE CANOPIES OR COVERS. B.C.C.: G.F.C.I. RECEPTICLE WIRED INCORRECTLY,(JETTED TUB RECEPTICLE). NEC: 336-18. NMC CABLE SHALL BE STAPLED WITHIN 12 IN. FROM BOX...MB
|
INSP - Ele Rough-In/Perm Svc | 1/8/1997 | 1/8/1997 | 1/8/1997 | P | PASS |
Marv Burrus
|
|
|
01/08/97 403 -
|