INSP - Permanent service | 3/25/1997 | 3/26/1997 | 3/26/1997 | P | PASS |
Jack Frank
|
|
|
03/26/97 315 - 53 ok jf 200a u/g new
|
INSP - Permanent service | 3/24/1997 | 3/25/1997 | 3/25/1997 | A | CANC |
Jack Frank
|
|
|
03/25/97 315 - need to check with JSchmer on 53 jf
|
INSP - Permanent service | 3/25/1997 | 3/25/1997 | 3/25/1997 | | FAIL |
Jack Frank
|
|
|
/ / 315 - 53 failed jf cor. posted NEC, T250-94 #4 to electrode and wa 250-80 shall remove #6 bond wire from sub panels,to water system, 110-14 use noalox on all alluminum connections, 250-92(b) use connector to pass through at service pan
|
INSP - Conference | 3/20/1997 | 3/20/1997 | 3/20/1997 | A | PASS |
Jim Schmer
|
|
|
Prefab house being inspected by State Elect. - City will do service only. - jms
|