INSP - Final | 4/28/1997 | 4/28/1997 | 4/28/1997 | P | PASS |
Marv Burrus
|
|
|
04/28/97 403 - KEY ABOVE GARAGE DOOR UNDER NUMBERS REINSPECTION --You wr ---JMS--- CORRECTIONS COMPLETED...MB
|
INSP - Final | 4/25/1997 | 4/25/1997 | 4/25/1997 | P | FAIL |
Marv Burrus
|
|
|
NEC: 336-6. N.M.C. CABLE BE SHALL BE PROTECETED FROM PHYSICAL DAM- AGE BY E.M.T. CONDUIT, FLEX CONDUIT, ETC...MB
|
INSP - Final | 3/27/1997 | 3/27/1997 | 3/27/1997 | A | PASS |
Marv Burrus
|
|
|
CORRECTIONS COMPLETED...MB
|
INSP - Ele Rough-In/Perm Svc | 3/26/1997 | 3/26/1997 | 3/26/1997 | P | FAIL |
Marv Burrus
|
|
|
NEC: 250-113 SHALL NOT USE METAL SCREWS TO GROUND ENCLOSURES...MB
|
INSP - Permanent service | 3/27/1997 | 3/26/1997 | 3/26/1997 | P | PASS |
Marv Burrus
|
|
|
ELE\R-I FAILED. NEC: 250-113.
|