INSP - Ele Rough-In/Perm Svc | 5/12/1997 | 5/12/1997 | 5/12/1997 | P | PASS |
Marv Burrus
|
|
|
05/12/97 403 - reinspection late pm today CORRECTIONS COMPLETED...MB
|
INSP - Ele Rough-In/Perm Svc | 4/25/1997 | 4/28/1997 | 4/28/1997 | P | FAIL |
Marv Burrus
|
|
|
04/28/97 403 - GARAGE AND SERVICE NEC: 210-8(A)(2). GARAGE SHALL HAVE G.F.C.I. PROTECTION. NEC: 225-8(B) EACH BUILDING SHALL HAVE DISCONNECTING FOR UNGROUNDED CONDUCTORS. NEC: TWO OR MORE BUILDINGS, EACH SHALL BE SUPPLIED BY GROUNDING ELECTRODE CONDUCTOR...MB
|