INSP - Permanent service | 6/13/1997 | 6/16/1997 | 6/16/1997 | A | PASS |
Marv Burrus
|
|
|
06/16/97 403 - re-inspection. CORRECTIONS COMPLETED...MB
|
INSP - Permanent service | 6/6/1997 | 6/9/1997 | 6/9/1997 | A | FAIL |
Marv Burrus
|
|
|
06/08/97 403 - NEC: 250-80. WATER PIPING SHALL BE BONDED TO SERVICE. N MORE BUILDINGS SHALL EACH HAVE A GROUNDING ELECTRODE SYSTEM. NEC: 230-2 SERVICE MAST SHALL BE GUYED OR BRACED.
|