INSP - Final | 3/25/1998 | 3/27/1998 | 3/27/1998 | P | PASS |
Marv Burrus
|
|
|
03/27/98 403 - Scheduled by Hello!. Contact phone is [4674018]. CORREC SUB-PANELS; DISCONNECTS.
|
INSP - Final | 2/20/1998 | 2/23/1998 | 2/23/1998 | P | FAIL |
Marv Burrus
|
|
|
02/23/98 403 - doherty elec ###-#### at 3:30 TABLE C1A. 3/0 CABLE IN 2IN. EMT CONDUIT--5 ea. ALLOWED, (CONDUIT TO FULL). 110-3. USE OF EQUIPTMENT. STRANDED WIRE WRAPED AROUND SCREW TERMINAL, (NOT ALLOWED PER JSCHMER.).
|
INSP - Final | 2/20/1998 | 2/20/1998 | 2/20/1998 | P | CANC |
Marv Burrus
|
|
|
school 467*4018 conf CONTRACTORS REQUEST. WILL RESCHEDULE.
|