INSP - Final | 2/27/1998 | 2/27/1998 | 2/27/1998 | P | PASS |
Jack Frank
|
|
|
###-####rein ok jf cor. made 200 o/h rec.
|
INSP - Final | 2/26/1998 | 2/26/1998 | 2/26/1998 | P | FAIL |
Jack Frank
|
|
|
02/26/98 315 - jack has no number will leave unlocked cor. posted 310-15 note #8 derate for 50% conduit fill, 110-3(b) use manufactures breakers only, 250-23 isolate grds and neutrals at sub pane house, 250-81 terminate grd within 5ft of where water pipe enters
|
INSP - Final | 2/24/1998 | 2/25/1998 | 2/25/1998 | A | NH |
Jack Frank
|
|
|
02/25/98 315 - mike ###-#### 200 amp service..trans by JMS.. nalc need access to inside of house to inspect sub panel
|