INSP - Final | 2/16/1999 | 2/16/1999 | 2/16/1999 | P | PASS |
Pat Lass
|
|
|
02/16/99 336 - ok
|
INSP - Final | 2/11/1999 | 2/12/1999 | 2/12/1999 | A | FAIL |
Pat Lass
|
|
|
02/12/99 336 - 370-23 Box for hydro-massage tub outlet is required to be 370-17 (c) exception Requires the romex to be secured within 8" of the b 370-17 Requires both protection and securing romex when it enters a meta
|
INSP - Electrical Rough-In | 1/5/1999 | 1/6/1999 | 1/6/1999 | A | PASS |
Jack Frank
|
|
|
01/05/99 315 - ###-#### dave ì
|