Final | 12/22/2004 | 12/22/2004 | 12/22/2004 | P | PASS |
Bob Reichert
|
|
|
corrections made, told owner to provide gfci on outside of shop, provide panel schedule, and cover panel openings. ok to final
|
Final | 12/17/2004 | 12/17/2004 | 12/17/2004 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell 314.15 Outdoor boxes shall be in weatherproof style for lights, receptacles, and switches. 314.20 boxes shall be set back less than 1/4" in wall. 314.27(A) Outlet boxes for light fixtures in the ceiling shall be designed for the purpose. 210.8(A)(1) and(2) Bathroom and garage shall use GFCI type receptacles. 406.5(B) Metal faceplates shall be grounded. 406.4 and 404.10(B) switches and receptacles shall be held rigidly and supplied with covers and installed.110.12(C) Receptacles shall be unbroken. 110.3(B) Receptacles shall be wired correctly 12/17/2004 5:51:09 PM
|
Final | 11/9/1999 | 11/10/1999 | 11/10/1999 | A | FAIL |
Joe Ray
|
|
|
ADENAN--- ###-#### FN INSP Too many violations- tried to explain violations to home owner.
|
Electrical Rough-In | 10/22/1999 | 10/25/1999 | 10/25/1999 | P | PASS |
Joe Ray
|
|
|
This is for a conference Adnan ###-#### said that he spoke with you and that you would meet with him at 1pm P/S change 100 A to 200A
|