Information based on query as of Tuesday, July 2, 2024.
Permit Information
Permit NumberELE99-03822
StatusFinaled
Name BERHAMOVIC ADNAN &
Site Address 11219 W ABRAM DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/22/200412/22/200412/22/2004PPASS
DetailsBob Reichert
corrections made, told owner to provide gfci on outside of shop, provide panel schedule, and cover panel openings. ok to final
Final12/17/200412/17/200412/17/2004PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell 314.15 Outdoor boxes shall be in weatherproof style for lights, receptacles, and switches. 314.20 boxes shall be set back less than 1/4" in wall. 314.27(A) Outlet boxes for light fixtures in the ceiling shall be designed for the purpose. 210.8(A)(1) and(2) Bathroom and garage shall use GFCI type receptacles. 406.5(B) Metal faceplates shall be grounded. 406.4 and 404.10(B) switches and receptacles shall be held rigidly and supplied with covers and installed.110.12(C) Receptacles shall be unbroken. 110.3(B) Receptacles shall be wired correctly 12/17/2004 5:51:09 PM
Final11/9/199911/10/199911/10/1999AFAIL
DetailsJoe Ray
ADENAN--- ###-#### FN INSP Too many violations- tried to explain violations to home owner.
Electrical Rough-In10/22/199910/25/199910/25/1999PPASS
DetailsJoe Ray
This is for a conference Adnan ###-#### said that he spoke with you and that you would meet with him at 1pm P/S change 100 A to 200A