Permit Information
Permit NumberESC15-00957
StatusFinaled
Name JIM CONGER
Site Address 6012 N PIERCE PARK LN
Project NameBELMAR ESTATES
Customer Number 
ePlanReviewNo
Description
New subdivision development with installation of utilities, roads, sidewalks, and stormwater drainage facilities. Lots will be graded and prepared for SFH construction. SWPPP prepared and eNOI filed for CGP requirements. BMPs include stabilized construction entrance, vegetative buffer zone (Farmer's Union Canal and easement), inlet protection, and perimeter controls (fiber wattles). Site slopes gently to the south towards river. Will need to be sure to have contigency plan in case groundwater is encountered. SITE PREPARATION inspection REQUIRED
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
General Inspection2/12/20182/12/20182/15/2018 CANC
DetailsMichael Zawacki
DOC - Permit Finaled2/15/20182/15/20182/15/2018PPASS
DetailsMichael Zawacki
General Inspection1/26/20181/26/20181/26/2018 PASS
DetailsMichael Zawacki
One remaining home. Talked to developer a few weeks ago, soon as witches hats removed I will close permit.
General Inspection1/11/20181/11/20181/11/2018 PASS
DetailsMichael Zawacki
One home being built, rest of phase has final stabalization. Called Jim Conger and let him know he can pull out inlet protection. Once BMPs are removed permit can be closed.
General Inspection12/27/201712/27/201712/27/2017 PASS
DetailsMichael Zawacki
Last lot has house under construction. Interior work in progress,
General Inspection12/12/201712/12/201712/12/2017 PASS
DetailsMichael Zawacki
1 home still under construction. DIs still installed.
General Inspection11/27/201711/27/201711/27/2017 CANC
DetailsAndy J. Long
General Inspection11/10/201711/10/201711/13/2017 CANC
DetailsAndy J. Long
General Inspection10/26/201710/26/201710/26/2017 PASS
DetailsMichael Zawacki
Nearly complete.
General Inspection10/5/201710/11/201710/11/2017APASS
DetailsMichael Zawacki
Nearing final completion. No dirt or track out. Inlet protection is about half full, will probably need to be cleaned before end of fall.
General Inspection10/5/201710/5/201710/5/2017 CANC
DetailsAndy J. Long
General Inspection9/20/20179/20/20179/20/2017 CANC
DetailsAndy J. Long
General Inspection9/5/20179/5/20179/8/2017 CANC
DetailsAndy J. Long
General Inspection8/21/20178/21/20178/22/2017 CANC
DetailsAndy J. Long
General Inspection8/4/20178/4/20178/4/2017 CANC
DetailsAndy J. Long
General Inspection7/20/20177/20/20177/20/2017 CANC
DetailsAndy J. Long
General Inspection7/5/20177/5/20177/5/2017 CANC
DetailsAndy J. Long
General Inspection6/20/20176/20/20176/20/2017 PART
DetailsAndy J. Long
WIP on SFHs on Hacienda and Baron. DI bags still installed on subdivision storm drains.

Request is issued to Evans construction to complete clean up on staging and washout lot on Bagley.

General Inspection6/5/20176/5/20176/5/2017 CANC
DetailsAndy J. Long
General Inspection5/19/20175/19/20175/19/2017 CANC
DetailsAndy J. Long
General Inspection5/4/20175/4/20175/9/2017 PEND
DetailsAndy J. Long
To final this subdivision ESC permit:

- remove all temporary BMPs ( DI bags) in strom drains
- clean up concrete washout and staging area on Bagley.
- remove permit signs on completed & stabilized projects.
No significant trackout, no spills or discharges observed. No stockpiles on the street. Some active SFHs in progress by Downey and Evan construction
General Inspection4/19/20174/19/20174/19/2017 CANC
DetailsAndy J. Long
General Inspection4/4/20174/4/20174/5/2017 FAIL
DetailsAndy J. Long
Need to clean up and remove existing concrete washout and dumped materials. Correction request already issued to Evan Construction & Tahoe.
General Inspection3/20/20173/20/20173/21/2017 CANC
DetailsAndy J. Long
General Inspection3/3/20173/3/20173/3/2017 PEND
DetailsAndy J. Long
request for new concrete washout facility issued 3/2. RP for D. Evans construction said one would be installed by next week as well as street sweeping...
General Inspection2/16/20172/16/20172/21/2017 CANC
DetailsMelissa Jannusch
General Inspection2/1/20172/1/20172/6/2017 CANC
DetailsAndy J. Long
General Inspection1/17/20171/17/20171/19/2017 CANC
DetailsAndy J. Long
General Inspection12/30/201612/30/201612/30/2016 CANC
DetailsAndy J. Long
General Inspection12/15/201612/15/201612/15/2016 PASS
DetailsAndy J. Long
WIP on SFH by Z. Evans and Tahoe. Subdivision BMPs installed. No significant trackout or muddy runoff observed. All homes in framing phase or beyond, no concrete or excavation occuring. No corrections.
General Inspection11/30/201611/30/201611/30/2016 PASS
DetailsAndy J. Long
WIP on SFHs. Subdivision stormwater facilitiies installed and have sediment protection. Lots of activity, trackout and loose dirt from landscaping activity swept weekly. No trash issues, spills, or other violations observed. Lined concrete washout pit provided
General Inspection11/15/201611/15/201611/15/2016 CANC
DetailsAndy J. Long
General Inspection10/31/201610/31/201611/1/2016 CANC
DetailsAndy J. Long
General Inspection10/14/201610/14/201610/14/2016 CANC
DetailsAndy J. Long
General Inspection9/28/20169/29/20169/30/2016APASS
DetailsAndy J. Long
Numerous SFHs in progress permitted seperately. No subdivion work remaining. DI bags installed. Concrete washout provided. No discharges or trackout from subdivision.
General Inspection9/28/20169/28/20169/28/2016 CANC
DetailsAndy J. Long
rescheduled 9/29
General Inspection9/13/20169/13/20169/13/2016 PASS
DetailsEvan Jenkins
work is occuring on multiple SFH's on all flat lots. no issues observed
General Inspection8/29/20168/29/20168/29/2016 PASS
DetailsEvan Jenkins
Subdivision is clean. No ESC issues observed at this time.
Work occuring on multiple SFH's
General Inspection8/12/20168/12/20168/12/2016 PASS
DetailsEvan Jenkins
Random Inspection7/28/20167/28/20167/28/2016APASS
DetailsEvan Jenkins
work occuring on multiple SFH's. Subdivision is overall in good shape. No ESC conditions observed at this time
General Inspection7/27/20167/27/20167/27/2016 PASS
DetailsAndy J. Long
WIP on SFHs by Tahoe and Z. Evans Construction. Two concrete washouts provided, no areas of significant trackout . Sites have trash containment and are relatively clean/well kept. Storm drains fitted with sediment filter bags.
General Inspection7/12/20167/12/20167/12/2016 PART
DetailsEvan Jenkins
Multiple SFH's under construction. Concrete washout is near 50% full: needs maintenance. Minor trackout had occured from sundays rains. week curbs and sidewalks and parts of road.
No other issues observed
General Inspection6/27/20166/27/20166/27/2016 PART
DetailsEvan Jenkins
WIP: on multiple SFH's. Some minor troughout througthout site needs to be swept along with various sidewalk areas
General Inspection6/10/20166/10/20166/10/2016 CANC
DetailsAndy J. Long
General Inspection5/26/20165/26/20165/27/2016 PASS
DetailsAndy J. Long
WIP on SFHs at Belmar by Tahoe and Zach Evans Construction. DI bags installed, lined concrete washout utilized, and trash contained. No trackout or discharges within or outside of sub. No corrections issued.
General Inspection5/11/20165/11/20165/11/2016 PASS
DetailsAndy J. Long
Belmar SFHs in progress by Z. Evans Construction and Tahoe Homes that are permitted seperately. Sites are clean, no trackout or discharges outside of subdivision. Trash containers and designated concrete washout provided.
General Inspection4/21/20164/21/20164/21/2016 PASS
DetailsEvan Jenkins
Random Inspection3/31/20163/31/20163/31/2016PPASS
DetailsAndy J. Long
WIP on SFHs by Zach Evans Construction and Tahoe. Lined washouts being used, trash contained, and DI bags are installed. No major trackout. No spills or discharges.
Random Inspection2/23/20162/23/20162/23/2016PPASS
DetailsAndy J. Long
Subdivision work complete. SFHs have seperate ESC permits under ZEvan Const. and Tahoe Homes. DIs have inlet protection that has been maintained. No erosion or sediment coming off lots.

Corrections isssued to home builders for housekeeping (trash container/cement washout)
General Inspection1/26/20161/26/20161/26/2016PPART
DetailsAndy J. Long
WIP on north end of Belmar Estates has homes by Tahoe and Zach Evans construction. Significant amount of trackout and lack of house keeping, subdivision is unoccupied currently. DIs have protection.

Need to have street sweeper at end of the week.
General Inspection12/1/201512/1/201512/1/2015PPASS
DetailsAndy J. Long
Belmar roads and stormwater infrastructure is now complete. All new DIs have been fitted with sediment filter bags. No trackout from subdivision to Pierce Park. Perimeter to the south in general direction of slight slope is well vegetated with no surface waters in the area.

WIP on landscaping, subdivision fencing and some utility trenching for parcels.
General Inspection11/3/201511/3/201511/3/2015APASS
DetailsAndy J. Long
WIP on paving roads within already installed curbing. Also need to patch subdivision entrance at Pierce Park so there is some loose sediment currently that will be swept up completion. No discharges occuring, site perimeter is no longer being operated on and no sediment is leaving site and stormwater infrastructure has been installed. No corrections at this time, will monitor sweeping once road work is complete. No recent complaints received.
Tracking Control10/8/201510/8/201510/8/2015PPASS
DetailsAndy J. Long
All roads have now been covered by roadbase so significantly less hauling traffic going forward. Roads are being prepped for paving within site. Sweeping occured last night as requested, road looks better today. Entance was getting muddy from irrigation runoff down Pierce Park, a check dam has been made to dry to keep entrance dry and RP asked neighbor to control irrigation runoff if possible. Entrance covered with road base to cover mud area.

RP stated sweeping to occur today at noon and at end of day. Site to be inactive tomorrow. Approved.

Complaint Inspection10/7/201510/7/201510/7/2015PFAIL
DetailsAndy J. Long
Complaint called in regarding trackout to Pierce Park south of Hill Road.



Observation:

Bringing in dirt and road mix for road paving which will happen later this week, significant heavy truck traffic in and out of site.


Stabilized entrance was removed for utility installation, so now trackout is occuring.


Called developer/RP Jim Conger to request sweeping ASAP to reduce build up. Got vm, will check back...


Coir mats are installed on the storm drains.


CA paving is the contractor.

General Inspection9/22/20159/22/20159/22/2015PPASS
DetailsEvan Jenkins
WIP: No issues observed at this time. No trackout nor dust occuring from construction
General Inspection8/26/20158/26/20158/26/2015PPASS
DetailsAndy J. Long
WIP on sewer and utilities for new Belmar subdivision. Work is concentrated around single trench area so no fugitive dust issues observed. No dewatering discharges observed offsite. No trackout onto Pierce Park; ESC permit sign and CGP information is posted. Approved.

Site Preparation7/28/20157/28/20157/28/2015PPASS
DetailsAndy J. Long
Permit sign posted at entrance, SWPPP and NOI onsite.

Some initial grubbing and outbuilding demolition has occured. No fugitive dust observed. Initial BMPs installed. Will need to add material storage area and concrete washout for curb work.

Approved to excavate.
Site Preparation7/27/20157/28/20157/28/2015APEND
DetailsAndy J. Long
re-scheduled for PM ride-along