Permit Information
Permit NumberESC16-01108
StatusFinaled
Name THOMAS WELLS
Site Address 1267 N CLOVERDALE RD
Project NameWhite Clouds Sub # 2
Customer NumberSUB14-00066
ePlanReviewNo
Description
corner of Highwood Ave & N Azure St
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
General Inspection10/17/201810/17/201810/17/2018 CANC
DetailsMichael Zawacki
DOC - Permit Finaled10/17/201810/17/201810/17/2018PPASS
DetailsMichael Zawacki
Witches hats all removed.
General Inspection10/2/201810/2/201810/2/2018 PASS
DetailsMichael Zawacki
Still a witches hat on Tyra. Will final permit after it is removed.
General Inspection9/14/20189/17/20189/17/2018APASS
DetailsMichael Zawacki
Parking addition completed. Area still needs to be landscaped. Silt fence still along canal.
General Inspection9/12/20189/12/20189/14/2018 CANC
DetailsAndy J. Long
rescheduled
General Inspection8/24/20188/28/20188/27/2018APASS
DetailsMichael Zawacki
All homes in neighborhood complete. Lots at entrance by cloverdalr are still exposed.
General Inspection8/23/20188/23/20188/24/2018 CANC
DetailsAndy J. Long
rescheduled
General Inspection8/8/20188/8/20188/8/2018 CANC
DetailsAndy J. Long
General Inspection7/24/20187/24/20187/24/2018 PASS
DetailsMichael Zawacki
Last home under construction. All other lots completed and stable.
General Inspection7/9/20187/9/20187/9/2018 PASS
DetailsMichael Zawacki
One home under construction. Large pile of fill in front yard. Some dirt on road from tree palnting at corner of Azure & Highwood.
Random Inspection6/22/20186/22/20186/22/2018PPASS
DetailsMichael Zawacki
Neighborhood is clean. Neighborhood DIs still installed. Few homes remain under construction,majority of neighborhood sold and landscaped.
General Inspection6/8/20186/8/20186/8/2018 PASS
DetailsMichael Zawacki
Very few houses remain in development. Some dirt on streets from landscape crews. Site is overall in good condition.
General Inspection5/24/20185/24/20185/24/2018 PASS
DetailsAndy J. Long
WIP on SFHs at west end of Azure Street. Subdivsion near full. Storm drains still have sediment bags installed.

Trash contained at sites. No corrections at this time.
General Inspection5/9/20185/9/20185/9/2018PPASS
DetailsMichael Zawacki
Most homes complete. Concrete washout has been cleaned and removed, roll pan brought on site for final foundations. Construction site cleanup company hired to clean and remove trash. Temps also being hired for cleanup help.
General Inspection4/30/20184/30/20184/30/2018PPASS
DetailsAndy J. Long
WIP on SFHs in Whitecloud by Hayden Homes. Storm drains have sediment protection, designated concrete washout pan on site, ESC permit signs posted on active homes. Trash contained at each site. Approved.
General Inspection4/19/20184/19/20184/20/2018 CANC
DetailsMichael Zawacki
General Inspection4/4/20184/4/20184/4/2018 PASS
DetailsMichael Zawacki
WIP on multiple SFH. Little dirt leaving sites, area is mostly clean. Some lots have lots of lumber scraps. Port O Pottie tipped over at Irving and Highwood, will also check other development to see who it belongs to.
General Inspection3/15/20183/20/20183/23/2018PCANC
DetailsAndy J. Long
General Inspection3/15/20183/15/20183/15/2018 CANC
DetailsAndy J. Long
rescheduled
General Inspection2/28/20182/28/20182/28/2018PFAIL
DetailsMichael Zawacki
Site needs trash pickup. Some tras bins are overfull, other lots didn't have bin and have garbage laying all over lot. Was windy at time of inspection and trash was blowing down road. Lots of dirt on shoulder of road and sidewalks. Weather is supposed to be wet next few days and may cause an issue.
General Inspection2/15/20182/15/20182/16/2018 PART
DetailsMichael Zawacki
Lots of trackout. Looks like street has been swept but lots of dirt remaining.
General Inspection1/31/20181/31/20181/31/2018PPASS
DetailsMichael Zawacki
Hayden Homes - White Clouds manager Phil Yates 208.608.3691
Streets are much cleaner. Crew is on site picking up trash and cleaning dirt of roads and sidewalks. Trash is being put into trash boxes.
Tracking Control1/18/20181/24/20181/25/2018AFAIL
DetailsMichael Zawacki
Talked to RP and gave him more time.
Site wasn't cleaned.
Tracking Control1/16/20181/18/20181/18/2018APEND
DetailsMichael Zawacki
Severe Trackout.
Gave RP more time for cleanup. Rescheduled.
General Inspection1/11/20181/15/20181/16/2018AFAIL
DetailsMichael Zawacki
Excessive trackout onto Azure and sidewalks. Alleyway were homes are being built also covered in trackout. Old dry concrete needs to be removed from washout at corner of Azure & Highwood. Washout area needs gravel entrance, not just mud. Highwood also dirty but may be different builder, also going to talk to them. Contacted RP Thomas with Hayden Homes, 9:45 on 1-16, left message. Gave until Thursday since rain in forcast. Will issue SWO if area isn't taken care off.
General Inspection1/11/20181/11/20181/11/2018 CANC
DetailsAndy J. Long
rescheduled
General Inspection12/27/201712/27/201712/28/2017 CANC
DetailsAndy J. Long
General Inspection12/12/201712/12/201712/12/2017 PEND
DetailsMichael Zawacki
Old washout still piled next to current washout. O
Didn't see green permit signs at all active lots. Some trackout, inversion "snow" was covering most of site.
General Inspection11/24/201711/27/201711/27/2017AFAIL
DetailsMichael Zawacki
Washouts not cleaned up. Material on side of roads and sidewalks.
General Inspection11/17/201711/22/201711/24/2017APEND
DetailsAndy J. Long
check for new wash out and some green signs posted.
BMP Violation11/13/201711/17/201711/17/2017PPEND
DetailsAndy J. Long
compliance deadline for washout extended to next Wednesday.
General Inspection11/9/201711/13/201711/13/2017PFAIL
DetailsAndy J. Long
Need to remove concrete washout and clean up area. Material should be disposed of properly at landfill, pit has some stormwater collected in it.

Correction request issued to Hayden Homes RP Tom

Stormdrains have sediment protection. Framing in progress on SFHs on Azure. Trash containment provided.

No trackout out of sub.
General Inspection11/9/201711/9/201711/9/2017 CANC
DetailsAndy J. Long
Tracking Control10/23/201710/25/201710/30/2017APASS
DetailsMichael Zawacki
Cleaned up trackout and fixed washouts. Said they are trying to get sweepers to show up.
General Inspection10/23/201710/23/201710/23/2017PFAIL
DetailsMichael Zawacki
Excessive trackout on both sidewal and streets. Multiple old washouts overflowing and washout around them. Syman documented both in their inspection but neither fixed. Walked around with project manager and he said he will get ti done today. Will schedule follow up to see if done.
General Inspection10/19/201710/19/201710/23/2017 CANC
DetailsAndy J. Long
General Inspection10/4/201710/4/201710/4/2017 CANC
DetailsAndy J. Long
General Inspection9/19/20179/19/20179/19/2017 CANC
DetailsAndy J. Long
General Inspection9/4/20179/4/20179/5/2017 CANC
DetailsAndy J. Long
General Inspection8/18/20178/18/20178/18/2017 CANC
DetailsAndy J. Long
General Inspection8/3/20178/3/20178/3/2017 CANC
DetailsAndy J. Long
General Inspection7/19/20177/19/20177/19/2017 PASS
DetailsAndy J. Long
WIP on SFHs by Hayden Homes.

Granite Excavation no longer onsite, houses have seperate ESC permits. No discharges, spills or other issues. Trash containers provided, lined concrete washout is being utilized. No dust or significant trackout.

Approved.
General Inspection6/30/20176/30/20176/30/2017 PASS
DetailsAndy J. Long
WIP on SFHs in Whitecloud by Hayden Homes. No significant trackout to streets. DI bags installed on storm drains. Lined concrete washout pit being used at west end of Azure. No corrections requested.
General Inspection6/15/20176/15/20176/16/2017 CANC
DetailsAndy J. Long
General Inspection5/31/20175/31/20176/2/2017 PART
DetailsMelissa Jannusch
Correction: Concrete washout needs maintenance.

No trackout
Trash is contained
DI bags ok.
No other ESC issues
General Inspection5/12/20175/16/20175/17/2017PCANC
DetailsAndy J. Long
General Inspection5/12/20175/12/20175/12/2017 CANC
DetailsAndy J. Long
rescheduled
General Inspection4/19/20174/26/20175/1/2017APASS
DetailsMelissa Jannusch
Concrete washout has been maintenance.
Correction: clean trackout in subdivision
General Inspection4/18/20174/18/20174/19/2017 PASS
DetailsMelissa Jannusch
Left message with RP Thomas from Hayden homes. Other RP Jerry is longer responsible for the project. Request maintenance of concrete washout sweeping of trackout on Highwood and Irving and replacement of the DI bag near trackout area. The rest of the subdivision is ok.
General Inspection3/31/20173/31/20173/31/2017APASS
DetailsAndy J. Long
Hayden Homes working on SFHs. Concrete washout pit provided on NW corner of Azure.. Storm drain inlets have filter bag protection. No trackout or trash violations. Will need to install inlet protection when work begins on Azure.
Random Inspection2/24/20172/24/20172/24/2017PPASS
DetailsAndy J. Long
Site grading, infrastructue, and utility installation complete. Landscping between medians in progress. New DIs have sediment protection installed. No corrections rquested.
General Inspection11/29/201611/29/201611/29/2016PPART
DetailsAndy J. Long
Subdivision roads and utilities now complete and parcels preped for SFHs by Hayden HOmes. Permit and SWPPP info posted. No significant trackout, uncontained trash or spills observed. No activity at time of inspection

Corrections:
- install DI bags on all new storm drains. Will notifiy Hayden Homes for SFH requirements
- needed new concrete washout.
Conference9/23/20169/26/20169/28/2016APEND
DetailsAndy J. Long
no activity. Permit sing now posted. Need to install construction entrance by sign or provide paving schedule. No trackout. A rock entrance is installed at the NE corner of work area.
General Inspection9/23/20169/26/20169/26/2016ACANC
DetailsAndy J. Long
Site Preparation9/23/20169/23/20169/23/2016PCANC
DetailsAndy J. Long
data entry error
BMP Violation9/21/20169/23/20169/23/2016APART
DetailsAndy J. Long
Check on track out, construction eneterances--

No activity. No construction entrance installed. Permit sign and SWPPP now installed. No wind blown dust or equipment operating dust.
BMP Violation9/20/20169/21/20169/21/2016PPART
DetailsMike Jordan
check for dust control. Water truck on site, noted dust control in progress when on site this morning.

Did note track out onto irving and Cloverdale. A verbal correction was given to Hayden Homes to Sweep all track out and provide controlled construction enterance and exits with top dressing. Also noted no SWPPP or ESC permit sign posted. A reinspection has been scheduled for Friday Sept. 23rd.
BMP Violation9/20/20169/20/20169/20/2016PPART
DetailsAndy J. Long
No water truck on site and excessive dust plumes leaving site boundaries.

Verbal correction request to onsite foreman Jake with Granite Construction to halt work until water truck is onsite.

Work stopped, I provided new permit sign and waited for 15 minutes until water truck arrived.

Jake stated water truck will be onsite at least once per every 2 hours to hit the haul road between stockpile of drain rock and seepage trench.
BMP Violation8/25/20168/30/20168/30/2016APEND
DetailsAndy J. Long
check for location permit and SWPPP on site. Unable to locate at this time
General Inspection8/24/20168/25/20168/25/2016APART
DetailsAndy J. Long
No activity at site. No windblown dust issues observed. No trackout or spills. DI's have sediment bags.

Need to post permit sign and SWPPP info. Corrections in progress.
General Inspection8/23/20168/24/20168/24/2016PCANC
DetailsAndy J. Long
Check to see if fugitive dust issues. Warning issued 8/22

rescheduled for tomorrow AM
BMP Violation8/23/20168/23/20168/23/2016PPART
DetailsAndy J. Long
WIP on grading and earth moving. Observed dust plumes crossing project boundaries and no dust control water truck operating.

Discovered water truck was on site waiting for a flat tire repair, buit was operating previously.

Issued warning to RP Jerry to control dust and get the truck fixed ASAP. Remindinged him of ESC permit conditions. Will check site tomorrow for water truck in action.