Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR00-00419
StatusFinaled
Name GRINNELL FIRE PROTECTION
Site Address 4696 W OVERLAND RD
Project NameSPR HILLCREST BUS. CNTR
Customer Number 
ePlanReview 
Description
*HILLCREST BUSINESS CENTER* To install a fire sprinkler system in this existing building and new support structure overbuild of existing roof; addition of a barrel roof at South entry over new 1st floor vestibule & second floor expansion. Some restroom upgrade for accessibility compliance on first floor; and interior upgrades and other misc. items as per approved building construction plans, notes & attached plan review comments. LETTER OF AGREEMENT ON FILE CONCERNING TIME FRAME FOR SPRINKLER SYSTEM INSTALLATION; AREA SEPARATION WALL; TIME FRAME FOR CODE COMPLIANCE. Building Permit BLD99-03216 (DRH99-0056 & DRH99-0152) **JWA**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/9/20037/9/20037/9/2003PPASS
DetailsTroy Cobbley
please call before going ###-#### mick
INSP-Sprinkler Rough-in/Hydro6/20/20036/23/20036/23/2003PFAIL
DetailsTroy Cobbley
KERRY- ###-#### Provide new friction loss for the different anti-freeze backflow preventer. Provide asbuilts with all changes. Signs for all valves and all other close out items as listed on the review notes. Provide verification that the new front canopies do not require protection since they appear to have combustibles inside. Pendants are still too close to supply registers. Provide clearance for operation of the PIV. Provide hydro test certificates 6/23/2003 2:08:21 PM
INSP-Sprinkler Rough-in/Hydro6/20/20036/20/20036/20/2003PCANC
DetailsTroy Cobbley
contractor said the sprinkler piping has a leak so the hydro test could not be performed 6/20/2003 1:49:14 PM
INSP-Sprinkler Rough-in6/17/20036/18/20036/18/2003AFAIL
DetailsTroy Cobbley
kerry; Phone #: ###-#### Provide clamps on the FDC piping in the crawl space, remove tape from the sidewall heads in the second floor corridor, pendants are overspaced throughout the building. Sprinkler spacing is 149 sq. ft. max. Pendant sprinkler heads are less than one foot to supply registers thoughout the building as well 6/18/2003 11:50:26 AM
INSP-Sprinkler Rough-in6/26/20026/27/20026/27/2002APASS
DetailsTroy Cobbley
Underground flush OK 6/27/2002 10:26:48 AM
INSP-Sprinkler Rough-in/Hydro3/27/20023/28/20023/28/2002APART
DetailsRick Jackson
###-#### TODD underground hydro only - okay 3/28/2002 10:45:19 AM
INSP-Sprinkler Rough-in2/21/20022/21/20022/21/2002APART
DetailsTroy Cobbley
Added by Inspector: 430 On 2/21/2002 10:24:43 AM Underground supply line from tap to 5' outside of building OK for cover. Inspection of PIV and ductile to be later
INSP-Sprinkler Rough-in/Hydro2/19/20022/20/20022/20/2002PNR
DetailsTroy Cobbley
Inspection was to be for underground. Contractor cancelled because of trenching 2/20/2002 3:54:00 PM
INSP-Sprinkler Rough-in4/5/20014/6/20014/6/2001APART
DetailsJoe Tawney
###-#### Spklr rough in. 2 Rooms overspaced. Add protection under stairs. Provide min 1 ft clearance from supply registers or install inter mediate temp heads. 4/6/2001 4:09:21 PM