Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR00-00644
StatusFinaled
Name SIMPLEX
Site Address 6140 W CURTISIAN AVE
Project NameSAINT ALPHONSUS (BLD.#6)
Customer Number 
ePlanReview 
Description
St Al's Bldg # 6 - To install a new fire alarm system in a new medical office building. In addtion the 2nd and 3rd floors of the connecting bridge will be connected to the new alarm panel.
NOTE: Occupancy is not allowed under this permit. This permit is only for the shell and core areas of the building. Separate fire alarm permit(s) will be required for alarm modifications necessary as part of tenant improvements, before occupancy will be allowed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20021/24/20021/24/2002PFAIL
DetailsTroy Cobbley
Added by Inspector: 430 On 1/24/2002 7:39:29 PM No elevator recall works, provide as-built drawings at FACP and with the City, provide spot type detectors in beam pockets in electrical, phone/data, mechanical and elevator rooms, basement flow switch sends no signal, damper at device M1-31 in south basement does not operate when detector is smoked, 2nd, 3rd and 4th floor flow switches do not report nor does the main flow switch, 2nd floor flow switch is programmed as a tamper, basement north stair strobe does not work, no signals are being sent off site
FIR-Aging Inspection5/30/20015/30/20015/30/2001 CANC
DetailsJoe Tawney
Cancel permit still open 5/30/2001 2:23:27 PM