Permit Information
Permit NumberFIR00-00653
StatusExpired
Name SIMPLEX/GRINNELL
Site Address 12000 W EXECUTIVE DR
Project NameALM - EXECUTIVE WHSE
Customer Number 
ePlanReview 
Description
TO REPLACE AN EXISTING FAC PANEL AND UPGRADE SYSTEM TO PROVIDE REQUIRED SPRINKLER MONITORING FUNCTIONS.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/24/20027/25/20027/25/2002AFAIL
DetailsTroy Cobbley
Provide 19.5 ah batteries for panel, provide verification power supply will support the batteries, provide calculations of 14 awg wire for the notification circuit, provide verification that the HVAC units meet requirements of UMC 608 for not having duct smoke detectors 7/25/2002 9:40:50 AM
INSP-Conference12/28/200112/28/200112/28/2001ANR
DetailsTroy Cobbley
Added by Inspector: 430 On 12/28/2001 11:44:48 AM Notified the fire alarm contractor final inspection is required and to get set up