INSP-Final Inspection | 7/24/2002 | 7/25/2002 | 7/25/2002 | A | FAIL |
Troy Cobbley
|
|
|
Provide 19.5 ah batteries for panel, provide verification power supply will support the batteries, provide calculations of 14 awg wire for the notification circuit, provide verification that the HVAC units meet requirements of UMC 608 for not having duct smoke detectors 7/25/2002 9:40:50 AM
|
INSP-Conference | 12/28/2001 | 12/28/2001 | 12/28/2001 | A | NR |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 12/28/2001 11:44:48 AM Notified the fire alarm contractor final inspection is required and to get set up
|