Permit Information
Permit NumberFIR00-00668
StatusFinaled
Name SIMPLEX
Site Address 700 S CLEARWATER LN
Project NameALM-CH2MHILL
Customer Number 
ePlanReview 
Description
CH2MHILL - To install a manual fire alarm system in an existing building. To include sprinkler monitoring, smoke detectors for HVAC shutdown, and smoke detectors for door hold-open release in rated corridors on 1st and 2nd floors.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/22/20052/22/20052/22/2005PPASS
DetailsTroy Cobbley
Fire alarm finaled 2/22/2005 1:25:09 PM
INSP-Final Inspection1/22/20031/23/20031/23/2003PFAIL
DetailsRick Jackson
###-#### duct detectors weren't shown on plans/map and inspector will need to test for unit shutdown; knox box needed per plan review notes; need written plan to Dave Miller for elevator recall; provide map at panel and show relocation of FACP and NAC panels; duct detectors need remote LED's or signs on grid to show location 1/23/2003 5:25:41 PM
FIR-Aging Inspection12/13/200212/13/200212/19/2002 PART
DetailsRick Jackson
talked to Simplex office and they will look inot it 12/19/2002 10:39:25 AM