INSP-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 2/22/2005 1:25:09 PM
|
INSP-Final Inspection | 1/22/2003 | 1/23/2003 | 1/23/2003 | P | FAIL |
Rick Jackson
|
|
|
###-#### duct detectors weren't shown on plans/map and inspector will need to test for unit shutdown; knox box needed per plan review notes; need written plan to Dave Miller for elevator recall; provide map at panel and show relocation of FACP and NAC panels; duct detectors need remote LED's or signs on grid to show location 1/23/2003 5:25:41 PM
|
FIR-Aging Inspection | 12/13/2002 | 12/13/2002 | 12/19/2002 | | PART |
Rick Jackson
|
|
|
talked to Simplex office and they will look inot it 12/19/2002 10:39:25 AM
|