Permit NumberFIR01-00037
StatusFinaled
Name PROTEX
Site Address 8455 W WESTPARK ST
Project NameALM - SCP GLOBAL TECH
Customer Number 
ePlanReviewNo
Description
SCP GLOBAL TECHNOLOGIES - To provide a new fire alarm system in a new, 2-story, V-N, 18,962 sq. ft. addition to an existing 109,471 sq ft., fully sprinklered (for area increase), V-N, building. The system will include complete manual pulls, HVAC duct smoke detectors and complete a.v annunciation. Plans indicate no sprinkler monitoring by the new FAC panel. It is understood all required sprinkler monitoring for the building is presently provided by the existing FAC panel, which is to be replaced by the new panel in June, per upgrade agreement approved by Fire Department.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20016/22/20016/22/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 6/22/2001 8:58:24 AM
INSP-Alarm Testing5/15/20015/15/20015/15/2001PFAIL
DetailsJoe Tawney
Added by Inspector: 406 On 5/15/2001 3:54:07 PM Reinsp Fail NFPA 72, Fax of signals, Add one horn/strobe, Ded circiut for FACP, Check sound levels in RR's and conf rooms
INSP-Alarm Testing5/9/20015/10/20015/10/2001PFAIL
DetailsJoe Tawney
Scheduled by Inspector: 406 On 5/9/2001 3:27:24 PM Fail System not correct 5/10/2001 2:28:34 PM