INSP-Final Inspection | 12/8/2003 | 12/8/2003 | 12/8/2003 | A | PASS |
Rick Jackson
|
|
|
|
INSP-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 | A | FAIL |
Rick Jackson
|
|
|
need approved plans; 12 amp hr batteries; horn not installed; zones not per plans; need verification/listing of the blue flex conduit for use in underground for PIV tamper; NFPA 72 Record of Completion; zones not defined; need to verify 2nd phone line trouble; need proper smoke detector per plans; need circuit breaker location and lockout 8/15/2003 11:45:18 AM
|
FIR-Aging Inspection | 8/31/2001 | 8/31/2001 | 8/31/2001 | | NR |
Rick Jackson
|
|
|
work not ready for inspection 8/31/2001 7:22:17 AM
|