INSP-Final Inspection | 5/13/2002 | 5/15/2002 | 5/15/2002 | P | PASS |
Rick Jackson
|
|
|
CHARLIE ###-####
|
INSP-Final Inspection | 3/6/2002 | 3/7/2002 | 3/7/2002 | P | FAIL |
Troy Cobbley
|
|
|
All devices at beginning of test not working. Stopped test. Complete new inspection to be called in 3/7/2002 2:30:22 PM
|
INSP-Final Inspection | 12/3/2001 | 12/6/2001 | 12/6/2001 | P | FAIL |
Troy Cobbley
|
|
|
HVAC units do not shut down immediately, need to test wall piv, set horn/strobe to temporal pattern, provide signs on doors, install sprinkler head in fire alarm room 12/6/2001 3:02:47 PM
|
FIR-Aging Inspection | 9/14/2001 | 9/14/2001 | 9/14/2001 | | NR |
Joe Tawney
|
|
|
No inspections have been made on this permit to date 9/17/2001 10:29:03 AM
|