Permit Information
Permit NumberFIR01-00346
StatusFinaled
Name PROTEX
Site Address 10531 W OVERLAND RD
Project Name 
Customer Number 
ePlanReview 
Description
COUNTRY SQUARE SHOPPING CENTER - To install a new fire alarm system within an existing, 1 story, sprinklered shopping mall. The alarm system will provide required offsite alarm monitoring of the sprinkler system and include monitoring of duct detectors for HVAC shut down. There is no building permit associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20025/15/20025/15/2002PPASS
DetailsRick Jackson
CHARLIE ###-####
INSP-Final Inspection3/6/20023/7/20023/7/2002PFAIL
DetailsTroy Cobbley
All devices at beginning of test not working. Stopped test. Complete new inspection to be called in 3/7/2002 2:30:22 PM
INSP-Final Inspection12/3/200112/6/200112/6/2001PFAIL
DetailsTroy Cobbley
HVAC units do not shut down immediately, need to test wall piv, set horn/strobe to temporal pattern, provide signs on doors, install sprinkler head in fire alarm room 12/6/2001 3:02:47 PM
FIR-Aging Inspection9/14/20019/14/20019/14/2001 NR
DetailsJoe Tawney
No inspections have been made on this permit to date 9/17/2001 10:29:03 AM