Permit NumberFIR01-00354
StatusFinaled
Name SIMPLEX
Site Address 8775 W USTICK RD
Project NameALM-
Customer Number 
ePlanReview 
Description
COLE VALLEY CHRISTIAN SCHOOL - To install a new fire alarm panel and system within an existing school. The preliminary design for this system layout was approved under FIR00-00534. Proposed work includes replacement of the existing fire alarm panel with an upgraded model which can support the required new alarm devices. Replacement of a fire alarm panel requires a review of the entire existing alarm system and upgrade of existing deficiencies to meet current code. A letter of intent to upgrade the existing alarm system deficiencies over a two-year period was approved by the BCFD 10/13/2000.
The new alarm system is designed to include required offsite sprinkler monitoring, a manual alarm system, partial area smoke detection, and a/v annunciation within Area 1, which is phase 1 of the upgrade agreement, and to connect to all existing devices in Area 2. No modifications are to be made in Area 2, which will be upgraded at a later date, per the approved upgrade agreement.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/21/200210/21/200210/21/2002APASS
DetailsTroy Cobbley
fire alarm finaled
INSP-Alarm Testing6/19/20026/19/20026/19/2002PFAIL
DetailsTroy Cobbley
provide a knox key box and an updated map 6/19/2002 3:36:52 PM
INSP-Final Inspection4/30/20024/30/20024/30/2002PFAIL
DetailsTroy Cobbley
relocate two smoke deectors in classrooms, add smoke detector in electrical room change programing for hvac shutdown upon any smoke detector activation 4/30/2002 4:55:14 PM
INSP-Alarm Testing9/17/20019/20/20019/20/2001PFAIL
DetailsJoe Tawney
Final Fail Some changes in system necessary 9/20/2001 5:55:37 PM