INSP-Final Inspection | 11/7/2001 | 11/7/2001 | 11/7/2001 | A | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/7/2001 9:44:07 AM OK for perm occ
|
INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/29/2001 | 10/29/2001 | P | FAIL |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 10/29/2001 4:03:57 PM Existing Area- 12' max storage heights exceeded. Need 4 way EQ brace in storage and show rooms. Need to center heads under all doors. In existing repair area heads to far from bottom of joistes and pipe hits garage door.Acc. area sidewall and pendant heads to far from walls. Attic area above lounge, heads overspaced. Mech unit in attic blocks head. Repair tenting in attic.
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2001 | 8/2/2001 | 8/2/2001 | A | PART |
Joe Tawney
|
|
|
Ok on spklr rough in on new showroom and whse area on West side 8/1/2001 4:18:53 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/26/2001 | 7/27/2001 | 7/27/2001 | A | CANC |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 07/26/2001 at 13:09:59. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | FAIL |
Joe Tawney
|
|
|
Spklr rough on new showroom and service area. Draft stops , sway bracing, add one head, combustible concealed space 7/25/2001 12:17:30 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/19/2001 | 7/19/2001 | 7/19/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/19/2001 at 08:39:10. Contact: ###-####. plans not approved for west side. not approved for cover 7/19/2001 3:39:22 PM
|