INSP-Sprinkler Rough-in/Hydro | 4/30/2002 | 4/30/2002 | 4/30/2002 | P | PASS |
Troy Cobbley
|
|
|
zone 12 and 13 underground flush and hydro test OK (6" and 12") 5/1/2002 12:41:10 PM
|
INSP-Sprinkler Rough-in | 4/15/2002 | 4/15/2002 | 4/15/2002 | P | PART |
Rick Jackson
|
|
|
r/i sam ###-#### the 6 inch lines for future concourse are okay to cover; will need one more section to complete. will require flush and hydro 4/15/2002 3:03:40 PM
|
INSP-Sprinkler Rough-in | 3/8/2002 | 3/8/2002 | 3/8/2002 | P | PART |
Rick Jackson
|
|
|
sam ###-#### underground insp two six inch stubbed out of south wall; approximately 50 foot in length okay to cover 3/8/2002 3:08:07 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/14/2002 | 1/14/2002 | 1/14/2002 | P | PART |
Rick Jackson
|
|
|
for under ground mike-- ###-#### underground hydro complete; flush will occur at future date when drains are ready 1/14/2002 2:15:56 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/26/2001 | 12/26/2001 | 12/26/2001 | P | NR |
Troy Cobbley
|
|
|
Underground pipe flange wouldn't hold pressure 12/26/2001 3:20:34 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/20/2001 | 12/20/2001 | 12/20/2001 | P | NR |
Rick Jackson
|
|
|
UNDERGROUND\###-#### will reschedule for later date 12/20/2001 1:17:03 PM
|
INSP-Sprinkler Rough-in | 12/17/2001 | 12/18/2001 | 12/18/2001 | P | PART |
Rick Jackson
|
|
|
###-#### underground rough/in complete from building to main water feed; needs flush and hydro 12/18/2001 3:10:03 PM
|
INSP-Sprinkler Rough-in | 11/13/2001 | 11/14/2001 | 11/14/2001 | A | PART |
Rick Jackson
|
|
|
###-#### UNDERGROUND partial underground installed; need final 20 ft to building; okay to cover 11/14/2001 4:04:29 PM
|