Permit Information
Permit NumberFIR02-00057
StatusFinaled
Name T J MAXX 'N MORE
Site Address 8345 W FRANKLIN RD
Project NameSPR T J MAXX 'N MORE
Customer Number 
ePlanReview 
Description
T J MAXX 'N MORE To remodel a: 47,217 ft/2 retail sales tenant space, formerly occupied by Home Depot. All work to be done per approved plans on file. Fire sprinkler system is existing and will be modified for construction of and outside *storefront canopy (*under a separate building and fire permit), new interior partitions to separate retail area from storage area, creation of new dressing rooms, construction of one fire-rated corridor egress system & one nonrated exit access, office area, break room, and separate storage lay-away area, the installation of suspended ceiling system, the installation of draft stops. All Storage racks over eight feet or six feet for High Hazard commodities (UFC 8101.4.1.6), in height, will require separate permitting. NOTE: This building is fully fire Sprinklered for unlimited area provisions. Any alterations or modifications to the sprinkler system shall require a separate permit and be per NFPA #13-1999, red-lined plans, attached review comment and conditions list, as regulated by the fire This permit is attached to BLD02-00201.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20025/13/20025/13/2002PPASS
DetailsTroy Cobbley
fire sprinkler system finaled
INSP-Conference4/23/20024/23/20024/23/2002PDONE
DetailsTroy Cobbley
I notified Bob Knight with Shilo, by phone, that the earthquake bracing for the fire sprinkler system will need to be brought up to code. I will faxed the correction notice tomorrow.
INSP-Sprinkler Rough-in/Hydro4/16/20024/17/20024/17/2002APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/16/2002 at 11:50:01. Contact: ###-####. tiems from previous inspection complied with; discussed with GC door hardware; exit signs; fire extinguishers; alarm testing and requirements for occupancy 4/17/2002 11:53:10 AM
INSP-Sprinkler Rough-in/Hydro4/11/20024/11/20024/11/2002PFAIL
DetailsTroy Cobbley
pendant heads are over space on eastside north/south running wall. Pendant head needs to be added at soffit point and upright heads need to be added at soffit point above ceiling. Exact locations have been marked on approved plans. I told contractor its OK to cover other areas 4/11/2002 5:21:41 PM