Permit NumberFIR02-00105
StatusFinaled
Name M2 AUTOMATION
Site Address 200 N 4TH ST Unit: 303
Project NameALM-TERRACE PLAZA LLC
Customer Number 
ePlanReview 
Description
TERRACE PLAZA LLC - To install a new fire alarm system in an existing, partially sprinklered, 4 level building. The system will include monitoring of the partial sprinkler system, HVAC duct detectors for air handler shutdown, complete manual pulls, smoke and heat detection for elevator recall, supplementary selective area automatic smoke detection in common building hallways/corridors and complete audible/visual annunciation throughout the building. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing5/5/20045/11/20045/11/2004APASS
DetailsRick Jackson
Rick can we do this on tuesday may 11th at @8:00 am. Call me if this is a problem Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman tested the flow switch - okay; elevator controller not capable of secondary floor recall and will be required if the controller is upgraded 5/11/2004 8:27:09 AM
INSP-Final Inspection5/11/20045/11/20045/11/2004APASS
DetailsRick Jackson
Final inspection okay 5/11/2004 8:28:19 AM
INSP-Alarm Testing6/12/20026/17/20026/17/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 06/12/2002 at 08:29:38. Contact: ###-####. need keys for knox box; elevator has primary recall only; 6/17/2002 5:10:58 PM