Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR02-00162
StatusFinaled
Name SIMPLOT IND INC
Site Address 5369 W IRVING ST
Project NameALM-SIMPLOT IND INC
Customer Number 
ePlanReview 
Description
SIMPLOT IND INC - To modify an existing fire alarm sprinkler monitoring system to add monitoring of an additional valve tamper switch, a smoke detector above the FAC panel, a manual pull station, and a 60-hour battery supply, per requirements of a BCFD inspection. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20031/24/20031/24/2003APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection10/11/200210/14/200210/14/2002AFAIL
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 10/11/2002 at 14:18:55. Contact: ###-####. verify dedicated electrical circuit to FACP has been completed, clean up wiring in the FACP, verify batteries in FACP are supervised after the panel gets cleaned up, duct smoke detectors do nto activate the fie smoke dampers as per the review comments, change labeling on the new tamper switch 10/14/2002 10:49:08 AM
INSP-Final Inspection10/8/200210/10/200210/10/2002PCANC
DetailsTroy Cobbley
contractor cancelled 10/10/2002 3:14:33 PM