Permit Information
Permit NumberFIR02-00263
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR ST ALS-S TOWER 5TH FLOOR
Customer Number 
ePlanReview 
Description
(ST ALPHONSUS-SOUTH TOWER-5TH FLR, WEST HALF, PHASE I) To remodel the west 18,295 ft/2 portion of the existing 34,940 ft/2 5th floor, for Patient Care Rooms and support facilities. Fire sprinkler work is related to the construction of interior non-bearing, non-combustible, fire-resistive walls to create a 1-hour exit corridor system, patient rooms, isolation & treatment, equipment & supply storage, restrooms, staff facilities and suspended ceiling grid system. NOTE: This building is fully fire sprinklered. This building is fully fire sprinklered. The fire sprinkler system work shall comply with NFPA 13?1999, attached review comment and conditions list; as regulated by the fire chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-00728.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/14/20032/14/20032/14/2003PPASS
DetailsTroy Cobbley
fire sprinklers finaled
INSP-Sprinkler Rough-in/Hydro1/28/20031/29/20031/29/2003APART
DetailsTroy Cobbley
###-####. Sprinkler piping is ok to cover from the west side fire doors all the way to the end of the building except for the west elevator lobby. One storage room and a cleaner storage room have sprinkler heads that are over spaced and several hangers need to be added. These locations are marked on the approved sprinkler drawings. 1/29/2003 10:27:22 AM
INSP-Final Inspection10/29/200210/30/200210/30/2002APART
DetailsTroy Cobbley
inspection was for sprinkler heads in laundry chute. heads are blocked by a flange that will need to be cut back before approved 10/30/2002 12:17:12 PM